FLS Director immediately conducts a rapid assessment of existing conditions.
ACTION |
Check FCC Alarm Panel and other devices. |
WHO |
FLS Director |
HOW |
Visual check. |
WHY |
To identify type(s) of Alarm and location within Building. |
ACTION |
Notify Fire Department. |
WHO |
FLS Director |
HOW |
Call 911. |
WHY |
State the following information:
|
ACTION |
Activate Fire Brigade (Engineers). |
WHO |
FLS Director |
HOW |
Hand held radio, cell phone, or telephone. |
WHY |
Fire Brigade will respond to Floor below the reported Fire and report on conditions. |
ACTION |
Notify Property Management Office at 212-382-9350. |
WHO |
FLS Director |
HOW |
Hand held radio, cell phone, or telephone. |
WHY |
Provide information as described above. |
ACTION |
Make a PA Announcement on the affected Floors and request Floor Wardens to go to Warden Phones (if safe to do so). |
WHO |
FLS Director |
HOW |
PA System located at the FCC Warden Phones located on each Floor. |
WHY |
To provide and receive reports of conditions on affected Floors. |
ACTION |
Make a Building-wide Announcement including Stairway Speakers (4W’s). |
WHO |
FLS Director |
HOW |
Initial Building Announcement to be conducted from the Fire Alarm PA System located at the FCC.
Additional notification can be made via LiveSafe, Email or other Mass Notification System. |
WHY |
Provide Occupants all available information including:
|
ACTION |
Follow procedures set forth in the Building’s Fire Safety/EAP Plan. |
WHO |
FLS Director |
HOW |
Be guided by procedures in FLS Plan. |
WHY |
FLS Plan Procedures have been established to limit the effects of a Fire/Smoke Condition. |
ACTION |
Recall Elevators to the Lobby. (If not already done.) |
WHO |
FLS Director
EAP Brigade Lobby Security Elevator Mechanic |
HOW |
Recall Elevators to Lobby Level in Phase I. |
WHY |
Gain/Maintain control of the movement of Building Occupants. |
ACTION |
Immediately shut down HVAC System at the FCC. |
WHO |
FLS Director
Building Engineers |
HOW |
Perform One-Point Shutdown at Fire Command Center. |
WHY |
Minimize air movement and prevent dissipation of smoke. |
ACTION |
Establish liaison with Emergency Responders. |
WHO |
FLS Director
Lobby Security Building Engineers |
HOW |
Meet arriving First Responders at Building Lobby. |
WHY |
|
* Simultaneous Notifications - Deputy Fire Life Safety Director and Pre-Designated Emergency Back-Up Personnel will assist in the Emergency Responses and Notifications.
FLS Director immediately conducts a rapid assessment of existing conditions.
ACTION |
Recall Elevators to the Lobby. (If not already done.) |
WHO |
FLS Director
EAP Brigade Lobby Security Elevator Mechanic |
HOW |
Recall Elevators to Lobby Level in Phase I. |
WHY |
Gain/Maintain control of the movement of Building Occupants. |
* Simultaneous Notifications - Deputy Fire Life Safety Director and Pre-Designated Emergency Back-Up Personnel will assist in the Emergency Responses and Notifications.
FLS Director immediately conducts a rapid assessment of existing conditions.
ACTION |
Recall Elevators to the Lobby. (If not already done.) |
WHO |
FLS Director
EAP Brigade Lobby Security Elevator Mechanic |
HOW |
Recall Elevators to Lobby Level in Phase I. |
WHY |
Gain/Maintain control of the movement of Building Occupants. |
ACTION |
Control Access to and Egress from Building. |
WHO |
Lobby Security
Any Fire Safety Staff |
HOW |
Position F/S Staff at all points of Access/Egress. |
WHY |
|
ACTION |
Establish liaison with Emergency Responders. |
WHO |
FLS Director
Lobby Security Building Engineers |
HOW |
Meet arriving First Responders at Building Lobby. |
WHY |
|
* Simultaneous Notifications - Deputy Fire Life Safety Director and Pre-Designated Emergency Back-Up Personnel will assist in the Emergency Responses and Notifications.
FLS Director immediately conducts a rapid assessment of existing conditions.
ACTION |
Control Access to and Egress from Building. |
WHO |
Lobby Security
Any Fire Safety Staff |
HOW |
Position F/S Staff at all points of Access/Egress. |
WHY |
|
* Simultaneous Notifications - Deputy Fire Life Safety Director and Pre-Designated Emergency Back-Up Personnel will assist in the Emergency Responses and Notifications.
FLS Director immediately conducts a rapid assessment of existing conditions.
ACTION |
Recall Elevators to the Lobby. (If not already done.) |
WHO |
FLS Director
EAP Brigade Lobby Security Elevator Mechanic |
HOW |
Recall Elevators to Lobby Level in Phase I. |
WHY |
Gain/Maintain control of the movement of Building Occupants. |
* Simultaneous Notifications - Deputy Fire Life Safety Director and Pre-Designated Emergency Back-Up Personnel will assist in the Emergency Responses and Notifications.
FLS Director immediately conducts a rapid assessment of existing conditions.
ACTION |
Immediately shut down HVAC System at the FCC. |
WHO |
FLS Director
Building Engineers |
HOW |
Perform One-Point Shutdown at Fire Command Center. |
WHY |
Minimize air movement and prevent dissipation of smoke. |
ACTION |
Establish liaison with Emergency Responders. |
WHO |
FLS Director
Lobby Security Building Engineers |
HOW |
Meet arriving First Responders at Building Lobby. |
WHY |
|
* Simultaneous Notifications - Deputy Fire Life Safety Director and Pre-Designated Emergency Back-Up Personnel will assist in the Emergency Responses and Notifications.