FLS Director immediately conducts a rapid assessment of existing conditions.
| ACTION |
| Immediately report to the FCC. |
| WHO |
| FLS Director |
| HOW |
| Most convenient way possible. |
| WHY |
| To make rapid assessment of the existing conditions. |
| ACTION |
| Notify Authorites and Emergency Responders. |
| WHO |
| FLS Director |
| HOW |
| Call 911 |
| WHY |
State the following information:
|
| ACTION |
| Announcement to CO Activation Floor and the Floors immediately above and below if Alarm is from 6th Floor and above. |
| WHO |
| FLS Director |
| HOW |
| PA System location at the FCC to 6th Floor and above. |
| WHY |
| Relocate Building Occupants to 3 Floors below their current work location. |
| ACTION |
| Announcement to CO Activation Floor and the Floors immediately above and below if Alarm is from 5th Floor and below. |
| WHO |
| FLS Director |
| HOW |
| PA System location at the FCC to 5th Floor and below. |
| WHY |
| Relocate Building Occupants to the designated Outside Assembly area. |
| ACTION |
| Make a Building-wide Shelter-in-Place Announcement including Stairway Speakers (4W's). SIP should apply to all occupants that have not been In-Building relocated or Evacuated under authority of previous annoucements. |
| WHO |
| FLS Director |
| HOW |
| PA System located at the FCC to entier Building Occupants. |
| WHY |
Provide Occupants all available information including:
|
| ACTION |
| Notify EAP Brigade to report to FCC. |
| WHO |
| FLS Director |
| HOW |
| Via Radio. |
| WHY |
| Conduct an initial assessment of the Emergency based on all available information. |
| ACTION |
| Manually release all Doors controlled by the Fail-Safe Electro-Magnetic System. |
| WHO |
| FLS Director |
| HOW |
| Manually released at FCC. |
| WHY |
| To ensure all Doors controlled by the Fail-Safe System are released. |
| ACTION |
| Manually recall Freight Elevators and Elevators serving the Floors on which the CD Sensor has been activated. |
| WHO |
| FLS Director
EAP Brigade Lobby Security Elevator Mechanic (as per Building’s Plan and infrastructure) |
| HOW |
| Via Fireman Service Lobby Key Switch or Elevator Management System (EMS), recall Freight Elevators to Street Level or area closest for NYPD/FDNY access. |
| WHY |
| Used to transport NYPD/FDNY Personnel and Persons needing assistance. |
| ACTION |
| Notify the JSOC at 212-417-7116 and the Property Management Office 212-483-0771 . |
| WHO |
| FLS Director Security |
| HOW |
| Handheld radio, cell phone or telephone. |
| WHY |
| Provide information as described above. |
| ACTION |
| Determine EAP Response relative to the Floors involved. |
| WHO |
| FLS Director EAP Brigade |
| HOW |
| EAP Brigade “Huddle” at FCC:Ascertain as much information as possible and assess available Response. |
| WHY |
| Provide protection and warning to the greatest number of Persons possible. |
| ACTION |
| Implement EAP Response. |
| WHO |
| FLS Director |
| HOW |
| Inform Building Staff Members which EAP Response is being implemented and instruct them to report to their assigned area to carry out their duties. |
| WHY |
| Ensure the safety of the greatest number of Persons possible. |
| ACTION |
| Manually Recall/Isolate Elevators based upon your assessment. |
| WHO |
| FLS Director
EAP Brigade Lobby Security Elevator Mechanic (as per Building’s Plan and infrastructure) |
| HOW |
| Via Fireman Service Lobby Key Switch or Elevator Management System (EMS) recall Elevators to Lobby Level or alternate Floor. |
| WHY |
| If it is required to mitigate the air movement within the Elevator Shaft and to prevent Occupants from using them in an uncontrolled Evacuation. |
| ACTION |
| If Persons are injured implement Medical Emergency Procedures as well. |
| WHO |
| FLS Director
EAP Brigade |
| HOW |
| As per Medical Emergency tab. |
| WHY |
| Ensure Persons receive necessary basic First Aid Medical assistance as quickly as possible prior to arrival of EMS.
|
| ACTION |
| Maintain two-way communication with EAP Staff. |
| WHO |
| FLS Director |
| HOW |
| Portable Radios, Warden Phones. |
| WHY |
| To monitor conditions and report on progress of operation. |
| ACTION |
| Follow up PA Announcements. |
| WHO |
| FLS Director |
| HOW |
| PA System at FCC. |
| WHY |
| To provide Building Occupants with any updated information. |
| ACTION |
| Liaison with Emergency Responders. |
| WHO |
| FLS Director
EAP Brigade Building Engineers Security |
| HOW |
| Through Incident Commander. *For this type of incident, this will be the highest ranking Fire Fighter/Police Officer on scene. |
| WHY |
|
FLS Director immediately conducts a rapid assessment of existing conditions.
| ACTION |
| Manually Recall/Isolate Freight Elevators and Elevators serving the Floors on which the CO Sensor has been activated. |
| WHO |
| FLS Director
EAP Brigade Lobby Security Elevator Mechanic (as per Building’s Plan and infrastructure) |
| HOW |
| Via Fireman Service Lobby Key Switch or Elevator Management System (EMS) recall Elevators to Street Level or area closest for NYPD/FDNY access. |
| WHY |
| Used to transport NYPD/FDNY Personnel and Persons needing assistance. |
| ACTION |
| Determine EAP Response relative to Floors involved. |
| WHO |
| FLS Director
EAP Brigade |
| HOW |
| EAP Brigade “Huddle” at FCC: Ascertain as much information as possible and assess available Response. |
| WHY |
| Provide protection and warning to the greatest number of Persons possible. |
| ACTION |
| If Persons are injured implement Medical Emergency Procedures as well. |
| WHO |
| FLS Director
EAP Brigade |
| HOW |
| As per Medical Emergency tab. |
| WHY |
| Ensure Persons receive necessary basic First Aid Medical assistance as quickly as possible prior to arrival of EMS. |
| ACTION |
| Liaison with Emergency Responders. |
| WHO |
| FLS Director
EAP Brigade Building Engineers Security |
| HOW |
| Through Incident Commander. * For this type of incident, this will be the highest ranking Fire Fighter/Police Officer on scene. |
| WHY |
|
FLS Director immediately conducts a rapid assessment of existing conditions.
| ACTION |
| Ensure location is physically isolated if possible to prevent further exposure/contamination. |
| WHO |
| Security
Any EAP Staff |
| HOW |
|
| WHY |
| Prevent any additional Person from entering contaminated area. |
| ACTION |
| Warn others to avoid the area. |
| WHO |
| Security
Any EAP Staff |
| HOW |
| PA System, RedFlag, E-Mail, Bullhorn from a safe distance if necessary. |
| WHY |
| Prevent contamination of any additional Persons/Staff. |
| ACTION |
| Assess/Monitor all Building Components. |
| WHO |
| Any EAP Staff |
| HOW |
| Members of the EAP Staff are assigned to assess a pre-determined Building Component according to the Building’s EAP. |
| WHY |
| Ensure all Building Components are assessed to allow for implementation of the EAP. |
FLS Director immediately conducts a rapid assessment of existing conditions.
| ACTION |
| Manually Recall Freight Elevators and Elevator serving the Floors on which the CO Sensor has been activated. |
| WHO |
| FLS Director
EAP Brigade Lobby Security Elevator Mechanic (as per Building’s Plan and infrastructure) |
| HOW |
| Via Fireman Service Lobby Key Switch or Elevator Management System (EMS) recall Elevators to Street Level or area closest for NYPD/FDNY access. |
| WHY |
| Used to transport NYPD/FDNY Personnel and Persons needing assistance.. |
| ACTION |
| Ensure location is physically isolated if possible to prevent further exposure/contamination. |
| WHO |
| Security
Any EAP Staff |
| HOW |
|
| WHY |
| Prevent any additional Person from entering contaminated area. |
| ACTION |
| Warn others to avoid the area. |
| WHO |
| Security
Any EAP Staff |
| HOW |
| PA System, RedFlag, E-Mail, Bullhorn from a safe distance if necessary. |
| WHY |
| Prevent contamination of any additional Persons/Staff. |
| ACTION |
| Notify the JSOC at 212-417-7116 Property Management Office at 212-483-0771. |
| WHO |
| FLS Director
Security |
| HOW |
| Hand held radio, cell phone, or telephone. |
| WHY |
| Provide information as described above. |
| ACTION |
| Manually recall/isolate Elevators based on your assessment. |
| WHO |
| FLS Director
EAP Brigade Lobby Security Elevator Mechanic (as per Building’s Plan and infrastructure) |
| HOW |
| Via Fireman Service Lobby Key Switch or Elevator Management System (EMS) recall Freight Elevators to Lobby Level or alternate Floor. |
| WHY |
| If it is required to mitigate the air movement within the Elevator Shaft and to prevent Occupants from using them in an uncontrolled Evacuation. |
| ACTION |
| Liaison with Emergency Responders. |
| WHO |
| FLS Director
EAP Brigade Building Engineers Security |
| HOW |
| Through Incident Commander. * For this type of incident, this will be the highest ranking Fire Fighter/Police Officer on scene. |
| WHY |
|
FLS Director immediately conducts a rapid assessment of existing conditions.
| ACTION |
| Access to and Egress from Building. |
| WHO |
| Security
Critical Operations Staff |
| HOW |
| Position EAP Staff at all points of Access/Egress. |
| WHY |
|
Standby and follow instructions of the FLS Director.
FLS Director immediately conducts a rapid assessment of existing conditions.
| ACTION |
| Notify Brookfield Corporate Office at 212-417-7000. |
| WHO |
| Property Manager
Assistant Property Manager Administrative Assistant |
| HOW |
| Telephone, Email, initiate RedFlag. |
| WHY |
| Provide information as described above. |
FLS Director immediately conducts a rapid assessment of existing conditions.
| ACTION |
| Manually Recall Freight Elevators and Elevators serving the Floors on which the CO Sensor has been activated. |
| WHO |
| FLS Director
EAP Brigade Lobby Security Elevator Mechanic (as per Building’s Plan and infrastructure) |
| HOW |
| Via Fireman Service Lobby Key Switch or Elevator Management System (EMS) recall Elevators to Street Level or area closest for NYPD/FDNY access. |
| WHY |
| Used to transport NYPD/FDNY Personnel and Persons needing assistance. |
| ACTION |
| Manually Recall/Isolate Elevators based on your assessment. |
| WHO |
| FLS Director
EAP Brigade Lobby Security Elevator Mechanic (as per Building’s Plan and infrastructure) |
| HOW |
| Via Fireman Service Lobby Key Switch or Elevator Management System (EMS) recall Freight Elevators to Lobby Level or alternate Floor. |
| WHY |
| If it is required to mitigate the air movement with the Elevator Shaft and to prevent Occupants from using them in an uncontrolled Evacuation. |
FLS Director immediately conducts a rapid assessment of existing conditions.
| ACTION |
| Engineers should respond to the relocation areas IF CO Sensor Activation is on upper Floor. |
| WHO |
| Building Engineers |
| HOW |
|
| WHY |
| Assess the physical condition of Building Occupants and initiate call for EMS if needed. |
| ACTION |
| Meet with FDNY at FCC if CO Activation is on Lower Floor where Occupants have evacuated the building. |
| WHO |
| Building Engineers |
| HOW |
Report to:
|
| WHY |
| To stop further CO emissions and/or perform other actions to ventilate the area. |
| ACTION |
| Assess Building's HVAC System ans Supplemental HVAC Units, shutting down the affected floor and the Floor above and below. |
| WHO |
| Building Engineers Tenant POC |
| HOW |
Report to:
|
| WHY |
| Closing Outside Air Dampers will prevent contamination of Building's Interior. |
| ACTION |
| Purge the Floors affected by the CO Activation and when directed to do so by the FDNY, introduce fresh air into the affected areas. |
| WHO |
| Building Engineers Tenant POC |
Report to:
|
WHY |
| Replaces purged areas with fresh air from the outside. |
| ACTION |
| Liaison with Emergency Responders. |
| WHO |
| FLS Director
EAP Brigade Building Engineers Security |
| HOW |
| Through Incident Commander. * For this type of incident, this will be the highest ranking Fire Fighter/Police Officer on scene. |
| WHY |
|
FLS Director immediately conducts a rapid assessment of existing conditions.
| ACTION |
| Assess Building’s HVAC System and Supplemental HVAC Units, shutting down the affected Floor and the Floors ABOVE and BELOW. |
| WHO |
| Building Engineers
Tenant POC |
| HOW |
|
| WHY |
| Closing Outside Air Dampers will prevent contamination of Building’s Interior. |
| ACTION |
| Purge the Floors affected by the CO activation and when directed to do so by the FDNY, introduce fresh air into the affected areas. |
| WHO |
| Building Engineers
Tenant POC |
| HOW |
|
| WHY |
| Replaces purged areas with fresh air from the outside. |
FLS Director immediately conducts a rapid assessment of existing conditions.
| ACTION |
| Assess all interior Stairways. |
| WHO |
| Any EAP Staff
Wardens Deputy Wardens |
| HOW |
| Position EAP Staff to Termination Points of Stairways (Lobby & Street Level) and individual Floor Landings. |
| WHY |
| Ensure all Stairways remain unobstructed to allow the movement of Building Occupants. |
FLS Director immediately conducts a rapid assessment of existing conditions.
| ACTION |
| Assess all interior Stairways. |
| WHO |
| Any EAP Staff
Wardens Deputy Wardens |
| HOW |
| Position EAP Staff to Termination Points of Stairways (Lobby & Street Level) and individual Floor Landings. |
| WHY |
| Ensure all Stairways remain unobstructed to allow the movement of Building Occupants. |